Power factor and harmonics are often discussed together because they share a cause: modern loads do not draw current in a simple way. In UAE facilities with many motors, drives, chillers and IT loads, both can affect running costs and reliability.
Power factor in plain terms
Power factor is the ratio between the real power that does useful work and the apparent power drawn from the supply. A low power factor means more current flows for the same useful output. That extra current heats cables and transformers and uses capacity you have paid for. Utility requirements for power factor apply in many installations, so check the rules for your connection.
What harmonics are
Harmonics are currents at multiples of the supply frequency. Variable frequency drives, UPS systems, LED drivers and IT equipment create them. Harmonics distort the voltage, overheat neutrals and transformers, and can cause nuisance tripping and failures in sensitive equipment. IEEE 519 is widely used as a reference for harmonic limits at the point of common coupling.
Measure first
A power quality survey with a class-rated analyser on the main incomers and key feeders records:
- power factor and reactive power over the full operating cycle,
- current and voltage harmonic distortion,
- voltage dips, swells and unbalance,
- loading of transformers and main feeders.
This is often part of an energy audit.
Solutions for low power factor
- Automatic capacitor banks: switch capacitor steps in and out with the load.
- Detuned capacitor banks: add reactors to avoid resonance where harmonics are present. This is the usual choice in buildings with many drives.
- Correct motor sizing: lightly loaded motors have poor power factor; right-sizing helps.
Solutions for harmonics
- Line chokes or DC chokes on drives reduce harmonic current at low cost.
- Active front-end or low-harmonic drives for large motors.
- Active harmonic filters that inject cancelling currents, useful where many mixed loads share a board.
- Passive filters tuned to dominant harmonics in specific installations.
Drive selection affects harmonics directly; see VFD selection for pumps and fans.
Keep monitoring
Install power meters with harmonic measurement on main boards and connect them to the BMS or energy system. Problems such as failed capacitor steps are then visible before they cost money.
Synthronix carries out power quality surveys and recommends and installs correction equipment. See our energy audit and management service.