For most buildings in Dubai, Abu Dhabi and the northern emirates, cooling is the single largest energy load. That makes the chiller plant the first place to look for savings. The good news is that many improvements come from how the plant is controlled, not from new equipment.
Measure before you optimise
You cannot tune what you cannot see. At a minimum, the BMS should read chilled water supply and return temperatures, flow, chiller power and pump power. With those values you can calculate the plant’s efficiency in kW per ton of cooling and see how it changes with load and weather.
If meters are missing, adding them is usually the first step. Our energy audit guide explains how audits identify these gaps.
Chiller staging based on real efficiency
Many plants stage chillers on simple rules, such as starting the next chiller when the leaving water temperature drifts. Better staging considers where each chiller is most efficient. Many modern chillers, especially those with variable speed compressors, run more efficiently at part load, so running two chillers at partial capacity can use less energy than one chiller at full load. The BMS can stage on calculated load and measured efficiency instead of temperature alone.
Chilled water supply temperature reset
A chiller uses less energy when it makes warmer water. At part load, the building often does not need the design supply temperature. A reset strategy raises the setpoint gradually while watching cooling coil valve positions. When valves approach fully open, the setpoint drops again. In the UAE, humidity control must be part of the logic so that coils still remove enough moisture.
Pump pressure reset
Variable speed secondary pumps usually hold a fixed differential pressure. Much of the time that pressure is higher than needed. A trim-and-respond reset lowers the setpoint until the most open valve is close to fully open, then holds it there. Lower pressure means lower pump speed, and pump power falls sharply as speed drops. If you are selecting new drives for this, see VFD selection for pumps and fans.
Condenser water control for water-cooled plants
For water-cooled chillers, the cooling tower fans and condenser water temperature trade off against each other. Colder condenser water helps the chiller but costs fan energy. The BMS can find a balance based on wet-bulb temperature and chiller load, within the limits the chiller manufacturer allows.
Fix low delta-T
A low temperature difference between supply and return water means the plant is pumping more water than it needs to. The causes are often on the coil side: valves that pass when closed, coils bypassing, or setpoints that are too low. The BMS trend data shows where the problem is, and fixing it improves both chiller and pump efficiency. On district cooling, a low delta-T can also affect what you pay.
Keep it working
- Calibrate the temperature and flow sensors that the strategies depend on.
- Review trends every season and after any plant change.
- Document every strategy in the sequence of operation so future teams understand it.
These strategies must be tested properly during BMS commissioning and reviewed after the first summer.
Synthronix programs and commissions chiller plant controls as part of our BMS contracting work, and combines them with energy audits and metering when the owner wants to measure the result.