MEP & maintenance

BMS and ELV AMC: what an annual maintenance contract should cover

An AMC is only as good as its scope. These are the items that separate a contract that keeps systems healthy from one that only answers calls.

BMS and ELV systems drift over time. Sensors lose calibration, overrides are left in place, disks fill up and software falls behind. An annual maintenance contract (AMC) is meant to stop that drift. Whether it does depends on what the contract actually includes.

Start with a takeover survey

At the start of a new AMC, the contractor should survey the systems: what works, what is faulty, what is missing from the documents, and whether programs and licences are available. Faults found here are listed and priced separately, so the AMC starts from a known baseline.

Preventive maintenance scope for BMS

  • Check controller status, communication and error logs.
  • Verify critical sensor readings against calibrated instruments.
  • Stroke-test valves and dampers and check actuators.
  • Review alarms, overrides and schedules; remove forgotten overrides.
  • Review trends for poor control and suggest sequence tuning.
  • Back up programs and databases and store copies off site.

Preventive maintenance scope for ELV

  • CCTV: clean lenses and housings, check views, recording and retention. See CCTV in Dubai.
  • Access control: test readers, locks, door contacts and exit devices; review user lists.
  • PAVA: test zones, fault monitoring and batteries. See PAVA systems.
  • Network: check switches, UPS units and rack temperatures.

Response times and call-outs

The contract should define priority levels, for example critical, urgent and normal, with a response time for each, and state whether call-outs are unlimited or capped. Remote support can resolve many software issues quickly if secure remote access is agreed.

Spare parts

State whether the contract is comprehensive or non-comprehensive and list the parts included. For critical systems, agree a small on-site stock of common spares such as sensors, power supplies and I/O modules.

Software and cybersecurity

Include software updates where licences allow, password management, user account reviews and secure remote access. Systems on the building network should not keep default passwords.

Reports

After every visit, you should receive a report with checks done, readings, faults found, actions taken and recommendations. A yearly summary helps plan upgrades and budgets.

Compare contracts on scope, not price

Two AMC prices can cover very different work. Compare visit frequency, checklists, response times, spares and reporting. For pumps, use a dedicated pump maintenance checklist alongside the BMS and ELV scope.

Synthronix offers maintenance contracts for BMS, ELV, automation and pump systems, including systems installed by other contractors. See our BMS and ELV services or request an AMC proposal.

FAQ

Common questions.

Not covered here? Ask an engineer

What is the difference between comprehensive and non-comprehensive AMC?

A comprehensive AMC includes the cost of agreed spare parts. A non-comprehensive AMC covers labour and visits, with parts quoted separately. The contract should list exactly which parts are included.

How many preventive visits does a BMS need per year?

It depends on the size and criticality of the building. Quarterly visits are common for commercial buildings, with more frequent checks for critical facilities such as data centres and hospitals.

Can a new contractor maintain a system installed by someone else?

Yes, if the owner has the programs, backups, licences and drawings. A takeover survey at the start of the contract identifies faults and missing information.

Keep reading

All articles

Talk to an engineer

Need help with Building Management Systems?

Send drawings, a BOQ or photos of the existing system. Our engineers review it and reply with the next step.