In malls, hotels, towers and schools, the PAVA system is the voice of the building. Most of the time it plays music and announcements. In an emergency it tells people clearly what to do, which is why it is treated as a life safety system.
What PAVA stands for
PAVA means public address and voice alarm. The public address side handles paging, announcements and background music. The voice alarm side broadcasts pre-recorded evacuation or alert messages automatically when the fire alarm system triggers it, and allows live emergency announcements from a fireman’s microphone.
Standards and approvals
Voice alarm equipment is commonly specified to EN 54-16 for control equipment and EN 54-24 for loudspeakers, with design guidance from BS 5839-8. In the UAE, the building’s fire and life safety design must follow the UAE Fire and Life Safety Code of Practice and be approved by the relevant Civil Defence authority. Check the approved design and specification for your building before selecting equipment.
Zoning
A building is divided into zones so that messages can go to the right places. Phased evacuation, used in many towers, depends on it: an alert message on most floors and an evacuation message on the fire floor and those nearby. Zoning must follow the fire strategy.
Intelligibility
A loud message is not the same as a clear one. Glass, marble and high ceilings, common in UAE lobbies and malls, create reverberation that blurs speech. Good design uses more loudspeakers at lower power, the right speaker types for each space and careful placement. After installation, speech intelligibility is measured, usually as STI, in representative areas.
Monitoring and backup power
Voice alarm equipment monitors amplifiers, loudspeaker lines and the link to the fire alarm system, and reports faults. Standby batteries keep the system running for the period the design requires. Amplifier redundancy is often specified so one failure does not silence a zone.
Integration with the fire alarm system
The fire alarm panel sends signals to the PAVA system to start the right message in the right zones. These interfaces must be tested end to end during commissioning and again during routine maintenance.
Testing and maintenance
- Test every zone with live and pre-recorded messages.
- Check fault reporting by disconnecting a speaker line and an amplifier.
- Run on battery power for the specified duration.
- Record STI results and keep them with the handover documents.
Routine checks belong in the building’s maintenance contract. PAVA cabling and racks should also be planned with the rest of the ELV infrastructure.
Synthronix supplies, installs, tests and commissions PAVA systems as part of our ELV systems packages in the UAE.